NEC Wire Size Calculator

Enter your Voltage, Phase, Load Current, One-Way Distance, and a few other circuit details, and the NEC Wire Size Calculator tells you the recommended wire gauge that meets both ampacity and voltage drop requirements — along with your Actual Voltage Drop, Ampacity Requirement, and Wire Ampacity so you can verify everything checks out to code.

A
A

Load operating for 3+ hours continuously

ft
%

NEC recommends 3% maximum

Results

Recommended Wire Size

--

Ampacity Requirement

--

Actual Voltage Drop

--

Voltage Drop

--

Wire Ampacity

--

Max Breaker Size

--

Ampacity vs Requirements

Frequently Asked Questions

What is the NEC and why does wire sizing matter?

The National Electrical Code (NEC) establishes minimum safety standards for electrical installations. Proper wire sizing prevents overheating, fire hazards, and ensures adequate voltage delivery to equipment.

How do I determine the load current for my circuit?

Load current should be obtained from equipment nameplates or manufacturer specifications. For motors, use NEC Table 430.248 for full-load current ratings rather than nameplate values.

What's the difference between continuous and non-continuous loads?

Continuous loads operate for 3 hours or more continuously and require conductors sized at 125% of the load current per NEC 210.19(A)(1). Examples include lighting and HVAC systems.

Why is voltage drop important in wire sizing?

Excessive voltage drop reduces equipment efficiency and can cause malfunction. The NEC recommends limiting voltage drop to 3% for branch circuits and 5% total for feeders plus branch circuits.

How does ambient temperature affect wire sizing?

Higher ambient temperatures reduce wire ampacity. NEC Table 310.15(B)(2)(a) provides derating factors - for example, conductors in 40°C ambient must be derated to 82% of their base ampacity.

When do I need to derate for multiple conductors?

When more than 3 current-carrying conductors are in the same raceway or cable, apply derating factors from NEC Table 310.15(B)(3)(a). Neutral conductors carrying only unbalanced current don't count.

What's the difference between copper and aluminum conductors?

Aluminum conductors are lighter and less expensive but have higher resistance than copper. They require larger sizes to carry the same current and need special termination methods per NEC 110.14.

How do I account for termination temperature ratings?

Use the lowest temperature rating in the circuit - either the conductor insulation, device terminals, or overcurrent protection. Most standard devices are rated 60°C or 75°C, limiting the usable conductor ampacity.

More Electrical & Electronics Tools